Suppose an engineer must forecast the next 15-minute voltage at the end of a feeder. The latest voltage at that point is useful, but it does not describe the whole situation. An upstream voltage change, a local load ramp, and a switch operation can produce different futures even when the end-point voltage is currently identical. The immediate modelling question is therefore: how should measurements from several pieces of equipment become one time-ordered example without losing node identity, timing, or the network configuration?
This tutorial develops a fixed-feeder representation for that question. It separates raw telemetry from the model table, carries one small synthetic example through an issue-time join, and defines tests that could show whether joint sequence modelling is worth its cost. It is about forecasting a measured quantity at a later time. Estimating the unobserved current electrical state is a different problem, often addressed through state estimation and a network model. A review of distribution state estimation discusses sparse measurements, pseudo-measurements, and topology as central difficulties; those concerns remain relevant to the data preparation here, but a forecast must additionally respect what was known at its issue time (state-estimation survey).
First decide what one row means
Let the system be a hypothetical radial feeder with three monitored locations: head H, mid-feeder M, and downstream D. We want to predict downstream phase-A voltage magnitude at the end of interval t+1, using information available by a fixed data-quality deadline after interval t closes. All numerical values below are invented to expose representation choices; they are not operating data, a power-flow calculation, or a validated forecast.
Choose a 15-minute UTC grid. Each model row is a snapshot interval rather than an individual sensor message. itemPosition = t denotes the same interval for every location. A row can contain H_v_a_pu, M_v_a_pu, D_v_a_pu, M_net_p_mw, D_net_p_mw, and a confirmed tie-switch state. This gives the model an ordered sequence of joint snapshots, x_(t-L+1), ..., x_t, and a target D_v_a_pu at t+1. The input has shape L × F: L time intervals by F named fields. The target here is one scalar, though several carefully defined outputs are possible.
The choice of a 15-minute interval is part of the task, not a property of the equipment. Synchrophasor data, SCADA records, and meters can arrive at very different rates. A US Department of Energy primer describes PMUs reporting time-stamped phasors many times per second and phasor data concentrators aligning and checking those streams (DOE synchrophasor primer). Aggregating such data to 15 minutes would discard dynamics that matter for disturbance detection. Conversely, treating 15-minute meter readings as if they were simultaneous with a high-rate PMU sample would create false precision. This example is suitable only for a decision whose horizon and response time make 15-minute summaries defensible.
Specify each field before joining anything. Voltage magnitude needs a bus or measurement-point ID, phase, physical or per-unit basis, interval statistic, and quality code. net_p_mw needs a sign convention: here positive means net consumption and negative means net injection. A frequency measurement should be associated with its actual instrument and averaging rule; repeating one system-frequency value under every node name would create apparently rich but redundant features. The switch field is a confirmed physical position as of the issue time, not an operator command. If its status is disputed, that is a data-quality condition, not a third switch position.
| Table | Grain | Example fields | Why keep it |
|---|---|---|---|
| Raw observation | Device, channel, measurement time, version | Value, unit, quality, ingestion time | Preserves corrections and arrival delays. |
| Network inventory | Asset and effective-time interval | Bus, phase, feeder, line, switch mapping | Prevents a changed asset map being applied to old readings. |
| Issue manifest | Feeder, issue time, target time | Eligible target, input cutoff, topology version | Defines exactly what could be scored. |
| Model table | Feeder segment and interval position | Named values, age and validity fields, target column | Supplies a stable numerical and categorical sequence. |
The model table is derived from the first three; it is not the system of record. The distinction matters when a meter value is revised tomorrow or a switch report arrives five minutes late. The low-voltage observability deployment study describes device heterogeneity, missing readings, and mapping measurements to network points as practical integration problems, rather than details an estimator can safely ignore.
Join measurements as they would have appeared at the issue time
For a forecast issued at 10:17 UTC, use the interval ending at 10:15 UTC as t; the target is voltage at the end of the 10:15–10:30 interval. The service has waited two minutes after interval close for its data-quality deadline. A reading measured during the closed interval but first received at 10:20 cannot enter this forecast, even if its measurement timestamp says 10:10. Keep both the measurement time and the arrival or availability time. For each channel and interval, choose the latest valid version that had arrived by 10:17, using a deterministic revision policy. Build historical training examples by replaying this same rule. A retrospective join to the final cleaned historian would answer an easier question than the live service faces.
Here is a tiny synthetic replay for that 10:17 issue. The measurement timestamp identifies the end of each 15-minute aggregate; a later revision of the same aggregate is a separate version. The values are illustrative, and all listed records pass the assumed quality check.
| Channel | Measurement timestamp (UTC) | Available at (UTC) | Value | In the 10:17 input? |
|---|---|---|---|---|
H_v_a_pu |
10:15 | 10:15:40 | 1.006 | Yes |
M_v_a_pu |
10:15 | 10:16:10 | 0.993 | Yes |
D_v_a_pu |
10:15 | 10:20:00 | 0.976 | No: arrived after issue |
D_net_p_mw, initial version |
10:15 | 10:16:30 | 1.6 | Yes |
D_net_p_mw, corrected version |
10:15 | 10:18:00 | 1.7 | No: use the earlier version |
The resulting t row at 10:17 contains H_v_a_pu = 1.006, M_v_a_pu = 0.993, and D_net_p_mw = 1.6. It marks D_v_a_pu unavailable and fills its numerical slot using the predefined missing-value policy, with D_v_a_observed = 0; it does not insert 0.976 from the late record. If a valid older downstream voltage is carried forward instead, its age and observed/fill indicator must travel with it. The 10:30 target is joined later for training or scoring and never becomes part of this 10:17 input.
For high-rate devices, define the aggregation interval and statistic before fitting a model: perhaps median voltage magnitude and maximum deviation within the interval. A single mean can erase a brief excursion; a maximum can be dominated by a bad sample. Quality filtering and minimum coverage must be set in advance. For a lower-rate meter, a last-observation value should carry its age. Do not linearly interpolate using a reading from the future across a gap. That future reading would not have existed at the forecast origin. A practical policy might accept a value only while its age is at most two intervals and otherwise mark the channel unavailable; that two-interval rule is an illustrative design choice, not an industry standard.
Missingness deserves at least two pieces of information: a filled numerical value and an indicator that says whether the value was genuinely observed. For example, use a training-period median or a bounded last-known value for D_net_p_mw, plus D_net_p_observed and D_net_p_age_intervals. Without the indicator, a model cannot distinguish a normal median reading from a replacement inserted after a telemetry outage. Fit imputation values and normalisation statistics on the training period only. Record outage periods separately: an entire feeder losing communications is different from an isolated downstream channel failure, and the missingness itself may correlate with the event being forecast.
After joining, assert invariants rather than hoping the table looks plausible:
- One row exists per
(sequenceId, itemPosition), with positions increasing on the chosen UTC grid. - Every included observation was available by that row’s issue deadline.
- Every field has a documented asset, phase, unit, and aggregation rule; values from different voltage bases are not mixed without conversion.
- Each row’s topology version was effective and known at that issue time.
- The target at
t+1is excluded from inputs att, and targets with inadequate quality are excluded from scoring with a recorded reason.
An event-time sort alone does not satisfy the second condition. Nor does a plausible voltage trace prove that a device was mapped to the right bus. Keep a sample of source-record IDs in an audit manifest so individual model rows can be reconstructed.
A worked representation of interacting measurements
Consider a separate synthetic history in which every shown input arrived by its issue deadline. The switch state is confirmed as closed in both histories. The downstream voltage at the issue time is the same, but the upstream measurements and load paths differ. The t+1 column is an invented teaching label that is hidden from the model at issue time.
| Scenario | Interval | H_v_a_pu |
M_v_a_pu |
D_v_a_pu |
D_net_p_mw |
Switch | Future D_v_a_pu |
|---|---|---|---|---|---|---|---|
| A | t-2 |
1.010 | 0.999 | 0.981 | 1.2 | closed | — |
| A | t-1 |
1.009 | 0.997 | 0.978 | 1.4 | closed | — |
| A | t |
1.006 | 0.993 | 0.976 | 1.6 | closed | 0.969 |
| B | t-2 |
1.002 | 0.987 | 0.970 | 1.8 | closed | — |
| B | t-1 |
1.005 | 0.991 | 0.973 | 1.6 | closed | — |
| B | t |
1.008 | 0.995 | 0.976 | 1.4 | closed | 0.982 |
A rule using only the latest D_v_a_pu sees 0.976 in both scenarios and must make the same prediction. A model using the whole three-row vector can see that A’s head voltage is falling while its downstream load rises; B shows the opposite pattern. It may learn different forecasts, but these six made-up rows do not prove that such patterns are predictive on a real feeder. The distinction is mathematical: a one-field endpoint representation maps both histories to the same input, while the joint sequence keeps them distinct.
This toy also exposes two ways to encode the interaction without a transformer. An engineer could compute the current head-to-downstream difference, H_v_a_pu - D_v_a_pu, and the two-interval downstream load change. At t, those are 0.030 pu and +0.4 MW for A, versus 0.032 pu and -0.4 MW for B. The voltage difference by itself does little to separate these two rows; the load change does. A linear or tree model on those engineered features could be sufficient. The sequence model’s case becomes stronger only if the useful relationship depends on several ordered changes, operating regimes, or interactions that fixed lags and features fail to capture out of sample.
Now change the switch at t-1 in scenario B, while leaving the voltages numerically unchanged. The same named measurements can have a different electrical relationship after reconfiguration. A wide row does not automatically encode the graph. At minimum, include a trustworthy topology or switching-regime field when it was known at the origin. If the network can split, assets can move between feeders, or node sets change frequently, a fixed set of columns may become brittle. Define new sequence boundaries where continuity is no longer meaningful, or use a topology-aware architecture. A graph model can represent connectivity explicitly; it deserves a place in the comparison when transfers across configurations are central. A published time-synchronized graph state-estimation study investigates topology changes for state estimation, which is evidence that topology can matter, not evidence that its reported results carry over to this forecasting task.
Choose the representation to match the network and task
For a stable feeder with a modest fixed sensor set, one wide row per interval is transparent. Every feature name refers to a known point and phase, and missingness is visible. Its cost grows with the number of nodes, phases, and channels. A single model trained across many feeders would need a consistent column layout or a defined mapping into shared roles. Blindly assigning node_1, node_2, and node_3 by geographic sort can make node_2 mean electrically different things across feeders.
A long table with (time, node, channel, value) is attractive for variable node sets, but it does not by itself tell a temporal model which readings belong to the same system snapshot. Serialising each channel as the next event gives the model an arbitrary within-interval order unless node identity and time are carried explicitly. If the intended prediction is interval based, the data loader or architecture must aggregate or attend across the node set at each time before following its evolution. That is a different design from feeding consecutive wide snapshots to a temporal model.
Graph-time models use buses or devices as vertices and electrical connections as edges, potentially with phase and line attributes. They may be a better inductive bias if topology is well maintained and generalisation to unseen node layouts matters. Their own risk is that an inaccurate graph can be more harmful than a simple measured-history baseline. A physics-based estimator or power-flow model remains important where line parameters, switch positions, and boundary conditions are reliable and the task is compatible with those calculations. The choice is empirical and operational: representation quality, latency, data maintenance, and the required output all count.
| Candidate | What it sees | Good first use | Main blind spot to test |
|---|---|---|---|
| Persistence or seasonal rule | Latest target, perhaps calendar | Hard-to-beat reference for short horizons | Cannot use changing upstream conditions. |
| Linear or tree model with lags | Selected node histories and engineered differences | Moderate data, inspectable interactions | Fixed features may miss longer ordered patterns. |
| Physics-based calculation | Network parameters, state, and boundary inputs | Trustworthy topology and parameters | Errors in inventory or unavailable inputs. |
| Wide multivariate sequence model | Ordered joint snapshots | Stable node set; multi-interval interactions | No inherent electrical graph or constraint guarantee. |
| Graph-time model | Measurements and explicit connectivity | Variable or changing node relations | Depends on correct graph and more complex serving. |
This is also why the phrase grid foundation model should not be attached to a transformer trained on one feeder. Pretraining on broad data, transferring representations to new tasks, and generalising to new grids are separate claims requiring separate experiments. For the immediate forecast, the benchmark is whether a model improves a defined decision on held-out origins.
Turn the table into a falsifiable forecasting experiment
Begin with an origin manifest: one row for each eligible (feeder, issue_time, target_time, target_node, phase). Fix the target as downstream phase-A voltage magnitude one interval ahead. Record the target source and quality, the topology version, the channels available at issue time, and whether the origin is eligible for each candidate representation. Use the same manifest for every model. Otherwise, one model can look better simply because its data path silently drops difficult outage periods.
Split origins chronologically into development, validation, and untouched test periods. Windowing should occur after those boundaries are defined, with targets assigned to their proper period. A model may use earlier history to predict the first validation target, but its labels and fitted preprocessing statistics must not leak backward into training. A random split of highly overlapping windows would overstate independence. If the intended deployment spans new feeders, add a feeder-held-out test; a chronological split on familiar feeders measures a different kind of generalisation. Report both, rather than replacing one with the other.
For the first run, compare persistence (forecast = D_v_a_pu at t), a simple model with recent lags and head-to-downstream differences, and a joint temporal model using the same issue-time data. If the operator already runs a credible engineering forecast, include it. Add a graph-time method only if the data and scope justify its implementation. Keep the horizon, origins, target quality policy, and permissible covariates fixed. Give each method a reasonable validation budget; an un-tuned complex model versus a carefully tuned baseline, or the reverse, answers little. If the operational question is still whether to predict voltage magnitude, load change, or a switch event, settle that choice first; the grid target selection guide develops that separate decision.
Report mean absolute error in per-unit voltage and signed bias by target point and phase. Inspect the tails near any locally defined voltage decision threshold, because a small overall error can hide missed excursions. Report coverage: the share of eligible origins on which each method can issue a forecast under the actual missing-data policy. Slice errors by topology regime, load level, sensor outage, season, and time since a switch change. A model that improves the average only in well-instrumented, unchanged periods may not help the operations workflow. For uncertainty, use paired differences on the same origins and resample blocks such as feeder-days rather than treating overlapping 15-minute windows as independent draws.
The decisive ablation is about representation. Train the same temporal architecture with (a) downstream history only, (b) all measured nodes, and (c) all nodes plus availability and topology fields. If (b) adds no stable value over (a), more nodes have not justified their ingestion cost. If (c) helps only near reconfiguration, report that limited benefit. Compare against the lagged tree or linear model to test whether the sequence architecture contributes beyond better features. Then deliberately evaluate missing-channel and switch-change periods. These are proposed experiments, not results of an experiment already run.
Do a physical-plausibility review as well. Point forecasts can be numerically accurate on average while violating an operator’s expectations under particular configurations. Examine traces around large errors and changes, compare forecasted node differences with the observed network regime, and have domain engineers inspect the largest misses. A pure statistical forecast is not a substitute for protection, state estimation, or other established control-room safeguards.
Where Sequifier fits
Sequifier is a candidate for the wide multivariate sequence branch of this comparison. Its README describes row-oriented sequences with sequenceId, itemPosition, and feature columns, including real and categorical variables. The preprocessing guide documents windowing, explicit real_columns and categorical_columns, training-only normalisation when normalize_on_all_data: false, and chronological value_cutoff splits. These capabilities cover the fixed-feeder table after the as-of join and missingness policy have been implemented outside Sequifier.
A practical mapping is one sequence per feeder while the monitored points keep stable identities, one item position per regular interval, real columns for voltages, loads, ages, and observation indicators, and a categorical column for a confirmed mode or switch state. Preserve ordinary switch changes within that sequence so the model can learn and be tested around them; start a new sequence when an asset remapping or network split makes the fixed columns mean something different. An indicator can also be treated categorically if that is how the model interface is designed; its meaning must remain stable. Use one output column, D_v_a_pu, for the first experiment. For a causal next-interval task with L input rows, the documented preprocessing window_length must be at least L + 1 with max_target_offset: 1; training uses context_length: L and target_offset: 1. The training guide places input_columns and target_columns on the model interface and the target criterion in the dataset configuration. Verify the generated windows and target positions against the origin manifest before interpreting a score. Choose L by a held-out comparison rather than assuming the longest affordable history is best; the context-length guide gives a separate procedure for that choice.
Sequifier does not create the asset map, recover an unknown topology, perform a physically constrained power flow, or prove that all input values were available at the issue time. Those are upstream engineering and evaluation responsibilities. A more elaborate repeated-node encoding could be investigated separately, but this tutorial’s documented path is the fixed-column table. If that representation and the temporal model beat credible baselines on the held-out operational question, extend the experiment to more nodes and horizons. If they do not, keep the simpler system. Engineers who find the workflow useful can star the Sequifier repository.